RB-10004 with Relay Output
• Suitable for automatic detectors in
conventional technology
• Relay output with dry change-over
contact
• Screw terminals for secure
connection of multiple wires
• Mechanical theft protection can be
activated
Description
The Detector Relay Base RB-10004 with integrated detector and remains active until the alarm is reset on
relay output is designed for the easy connection of au- the fire detection control panel.
tomatic detectors Series ORBIS. Due to its robust multi-
wire screw terminals, the detectors can be wired with The base has been designed for surface mounting in
ease, thus achieving a secure and durable connection. dry rooms. For special applications a range of acces-
sories (for moist room, false ceiling or flush installation)
In addition, a relay output with a dry change-over contact is available.
is integrated into the detector base. The relay output is A mechanical theft protection of the detector can
activated through the alarm activation of the inserted optionally be activated at the detector base.
Specifications
Operating voltage
Current consumption
Contact rating
Ambient temperature
Relative humidity
Dimensions ø × H
Colour
Supply through the detector line voltage
7mA (active)
1A at 30VDC
-40°C to +70°C
10 – 98% (no condensation)
100 × 24 (mm)
white
Weight
80g
Order number
Order name
246041
Detector Relay Base/Conv./ORBIS/Apo RB-10004