Process Fluid Chiller
Designed for Marconi Medical MX8000
Keeping Business in Business
• Dedicated, equipment-matched cooling supplies the proper temperature and water flow year round.
• Factory-tested, piped, wired and charged for hassle-free startup and operation.
• Clean, non-ferrous cooling loop, required for sensitive medical equipment.
• Local service and parts for quick and knowledgeable maintenance and service.
• Optional switch-over to alternate water source provides redundant, continuous operation.
• Optional remote monitoring systems keep you informed of chiller operation.
• ETL/CSA certified.
• ISO 9001 certified company.
MX8000 Specifications
Fluid Specified
Water or Glycol
32,400 (9.5)
36-57 (2-14)
0.5°C/min
Max Heat Dissipation—BTUH (kW)
Fluid Temperature Range—°F (°C)
Temperature Gradient
Fluid Flow Rate—GPM (l/m)
Fluid Pressure Drop—PSI (kPa)
4.4 (16.7)
2.2 (15)
Process Fluid Chiller Specifications
Model Number
PS048A
Water
PS048A
PS048A
Propylene Glycol
36,500 (10.7)
48 (8.9)
Fluid Circulated
Ethylene Glycol
38,300 (11.2)
48 (8.9)
Net Cooling Capacity—BTUH (kW)
Leaving Fluid Temperature—°F (°C)
Fluid Flow Rate—GPM (l/m)
MX8000 Pressure Drop—PSI (kPa)
Chiller Pressure Drop—PSI (kPa)
Pump Total Head—PSI (kPa)
Head Available for Piping Circuit—PSI (kPa)
Pump HP (kW)
41,200 (12.1)
48 (8.9)
8 (30.4)
8 (30.4)
8 (30.4)
2.2 (15.2)
8.2 (56.5)
46.8 (322.7)
36.4 (251)
1 (0.75)
2.2 (15.2)
11.1 (76.5)
46.8 (322.7)
33.5 (231)
1 (0.75)
2.2 (15.2)
13.1 (90.3)
46.8 (322.7)
31.5 (217.2)
1 (0.75)
Process Fluid Chiller Designed for Marconi Medical MX8000
1
|