Liebert Switch HiSwitch2 User Manual

Power Quality Systems  
Liebert HiSwitch2  
Digital Static Transfer Switch  
 
Optional Color Touch-Screen Interface  
Standard LED Panel  
The controls of the HiSwitch2 are intuitive and simple. The  
pop-up menus are easy to understand and provide a wealth  
of operational and diagnostic information.  
This optional color LCD monitor is divided into three segments.  
In addition to a system mimic diagram, there is a Status/Alarm  
panel and a section dedicated to operator instructions and  
menus. You benefit from improved operator effectiveness,  
reduced training time, and less chance of operator error.  
In case you need simplified version of interface, the  
Standard LED Panel is a good and economic solution for the  
customer. It is possible to monitor the unit and alert when a  
problem occurs by means of a series of LEDs and buttons.  
Both optional and standard Panel solutions can be accessed  
from a terminal, or a PC running terminal emulation soft-  
ware, that is attached to the unit.  
03  
SYSTEM#1  
SYSTEM#2  
Liebert Experience: Greater Overall Value  
Bypass  
Mains  
Bypass  
Mains  
The design of the HiSwitch2 reflects our decades of leader-  
ship in critical power and environmental system architecture:  
Normal  
Mains  
Normal  
Mains  
Normal  
Mains  
Normal  
Mains  
Conservative design margins and excellent overload  
capacity. Can also be placed against a wall or partition.  
UPS #1 UPS #6  
UPS #1 UPS #6  
Designed for maintainability, with all power-train  
components removable and serviceable from the front,  
without shutting down the connected load.  
HiSync  
Internal CANBUS protocol: high-bandwidth communica-  
tion between system components via twisted-pair  
cables. Options can be added as simple network nodes.  
Full range of communications options to fit any  
monitoring strategy for the Optional LED Panel.  
HiSwitch2  
#1  
Critical Load  
Critical Load  
The Liebert Experience means a wider variety of power system  
solutions from one source. Ask your Emerson Network Power  
representative for information about Liebert range of Power  
Quality Solutions.  
HiSwitch2  
#2  
Dual Bus System Configuration  
All components are thoughtfully  
arranged for straight forward  
installation and maintenance.  
For units up to 600 amps, the  
entire power and control module  
can be removed as an assembly.  
Note the separate compartment  
for option modules, upper right,  
for safe and convenient field access.  
 
Technical Features [Liebert Hiswitch2]  
Rating (A)  
Dimensions (W x D x H)  
Weight*(kg)  
[mm]  
100  
250  
400  
600  
800  
1000  
762 x 813 x 1956  
762 x 813 x 1956  
965 x 813 x 1956  
965 x 813 x 1956  
2134 x 813 x 1956  
2134 x 813 x 1956  
354  
354  
544  
544  
1134  
1134  
*Note: Actual Weights will vary depending on installed options.  
Specifications  
Operating Specifications  
Rack-out control/power assembly on units up to 600A,  
to allow maintenance, service, or full replacement  
without disrupting the critical load  
Voltage: 208, 220, 240, 380, 400, 415 VAC  
(field selectable), +/- 10%  
3-pole configurations  
Frequency: 50 or 60 Hz (field selectable), +/- 5%  
Top and bottom cable entry  
Short-circuit Withstand Capability: 100kA at 208VAC,  
from 65kA to 100kA at 480VAC (depending on the rating)  
Dual-lug installation bus with pem nuts for  
single-hand installation and "hot" torque service  
Sense and transfer time: 5ms maximum  
Overload Capability: 125% for 10 minutes,  
150% for 2 minutes, 110% for 1 hour  
Optional Features*  
Full range of Open Comms™ hardware and software  
Internal modem for dialing out alarms to phone or pager  
Operating Temperature: 0 to 40° C  
Color touch-screen LCD interface  
eliminates mechanical pushbuttons  
Standard Features  
All components front accessible for installation  
and service; no side or rear access required  
Intuitive user interface with  
drop-down menus and dialog boxes  
Triple-redundant DSP digital logic  
Dual-redundant power supplies  
100% rated, fuseless design  
Programmable output relays for custom  
customer alarms and connections  
Customizable input relays allow alarms from other  
devices to be displayed on HiSwitch2 display  
Flash memory enables firmware updates  
while supporting critical load  
CANBUS internal control wiring  
*Compatible with LCD Panel only  
While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting  
from use of this information or for any errors or omissions. © 2004 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.  
All names referred to are trademarks or registered trademarks of their respective owners. ® Liebert and the Liebert logo are registered trademarks of the Liebert Corporation.  
® Keeping Business in Business is a registered trademark of the Liebert Corporation. The Emerson logo is a trademark and service mark of Emerson Electric Co.  
Liebert HIROSS UPS Sales Headquarters  
Via Leonardo da Vinci,8  
Liebert HIROSS Services Headquarters  
Via Leonardo da Vinci,8  
Emerson Network Power Ltd - UK  
Fourth Avenue, Globe Park - Marlow  
Buckinghamshire - SL71YG  
35028 - Piove di Sacco (PD)  
35028 - Piove di Sacco (PD)  
tel. +39 049 9719111 fax +39 049 9719317  
tel. +39 049 9719111 fax +39 049 9717053  
tel. +44 1628 403200 fax +44 1628 403203  
 

LevelOne Network Router WBR 5400 User Manual
LG Electronics Clothes Dryer DLEX3875V User Manual
LG Electronics Refrigerator LFX25971ST User Manual
Linear Speaker H588 6 User Manual
Linear Vacuum Cleaner AVP12000 User Manual
LOREX Technology Security Camera SG6350P User Manual
Marantz DVD Player DV4400 User Manual
Maytag Washer MAV5257 User Manual
Memorex MP3 Player MD6882 User Manual
Mercedes Benz Automobile C 240 User Manual