PSP722E
52026
®
LUXPRO EVERYTHING’STAT PSP722E
INSTALLATION AND OPERATING INSTRUCTIONS
1.
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPATIBILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HEAT STAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COOLING/COMPRESSOR STAGES . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTRICAL RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TOOLS REQUIRED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOVAL OF OLD UNIT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MOUNTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
2
2
2
2
2
2
3
3
3
3
3
4
4
4
4
4
4.1.4 MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.1.5 DISPLAY ILLUMINATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.
2.1.
2.2.
2.3.
3.
4.2.
USER SETUP MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.2.1 ACCESS AND NAVIGATE USER SETUP MENU. . . . . . . . . . . . . . . . . . . . 12
4.2.2 KEYBOARD LOCK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.2.3 BEEP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.2.4 TEMPERATURE DISPLAY FORMAT (F/C DISPLAY) . . . . . . . . . . . . . . . . 13
4.2.5 CLOCK FORMAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.2.6 CALIBRATION OFFSET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.2.7 MAXIMUM HEAT SETTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.2.8 MINIMUM COOL SETTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.2.9 SMART RECOVERY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.2.10 FILTER LIMIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.2.11 USER SETUP MENU: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1.
3.2.
3.3.
3.4.
3.5.
3.5.1 TERMINAL DEFINITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5.2 FREEZE PROTECTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5.3 SPECIAL WIRING NOTES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5.4 COMMON WIRING OPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5.5 SINGLE STAGE HEATING SYSTEMS LABEL CROSS REFERENCE. . . . .
3.5.6 SINGLE STAGE COOLING SYSTEMS LABEL CROSS REFERENCE . . . .
3.5.7 SINGLE STAGE FURNACE HEATING AND SINGLE STAGE
4.3.
ADVANCED FEATURES AND OPERATION . . . . . . . . . . . . . . . . . . . . 13
4.3.1 EMERGENCY HEAT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.3.2 FAN MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.3.3 VACATION HOLD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.3.4 DAYLIGHT SAVINGS TIME ADJUSTMENT (DST) . . . . . . . . . . . . . . . . . 14
4.3.5 AIR FILTER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.3.6 ENERGY USAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.3.7 FUTURE OUTDOOR SENSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.3.8 FUTURE REMOTE INDOOR SENSORS. . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.3.9 RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
COOLING SYSTEM LABEL CROSS REFERENCE . . . . . . . . . . . . . . . . . .
3.5.8 TWO STAGE HEAT, SINGLE STAGE COOL HEAT PUMP SYSTEM
LABEL CROSS REFERENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5.9 WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
5
5
9
9
9
3.6.
3.7.
INSTALL BATTERIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLER SETUP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.7.1 ACCESS AND NAVIGATE INSTALLER SETUP MENU . . . . . . . . . . . . . . .
3.7.2 INSTALLER SETUP MENU WITH
4.4.
PROGRAMMING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.4.1 WEEKDAY TEMPERATURE PROGRAMMING. . . . . . . . . . . . . . . . . . . . . 15
4.4.2 WEEKDAY FAN PROGRAMMING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.4.3 WEEKEND PROGRAMMING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.4.4 COPY PROGRAMMING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
FURNACE SYSTEM TYPE SELECTED: . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.7.3 INSTALLER SETUP MENU WITH HEAT
PUMP SYSTEM TYPE SELECTED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.7.4 COMPLETING YOUR INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.
BATTERIES/MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
BATTERY INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
TECHNICAL DETAILS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
STAGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
TECHNICAL ASSISTANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1.
6.
4.1.
OPERATING BASICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.1.1 UP/DOWN ARROW CHANGE KEYS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.1.2 SET DAY AND TIME . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.1.3 DEFAULT PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.1.
7.
8.
WARNING: Use Energizer® or DURACELL® Alkaline Batteries Only.
Energizer® is a registered trademark of Eveready Battery Company, Inc.
DURACELL® is a registered trademark of The Gillette Company, Inc.
l
●
On replacement installations, mount the new thermostat
in place of the old one unless the conditions listed below
suggest otherwise. On new installations, follow the
guidelines listed below.
Route the wires through the open areas in the base
plate above the terminals. Hold the base against the wall,
with the wires coming through. Position the base for the
best appearance (to hide any marks from an old thermo-
stat). Attach the base to the wall with the two screws pro-
vided.
●
Do not locate in a damp area. This can lead to corro-
sion that will shorten thermostat life.
●
Do not locate where air circulation is poor, such as in a 3.5. WIRING
corner or an alcove; or behind an open door.
3.5.1 TERMINAL DEFINITIONS
●
Do Locate the thermostat on an inside wall, about 5 ft.
Terminal Definition
(1.5m) above the floor, and in a room that is used often.
1
2
G
O
Fan
●
Do not install it where there are unusual heating condi-
Cooling Mode
tions, such as: in direct sunlight; near a lamp, radio, tele-
vision, radiator, register, or fireplace; near hot water pipes
in a wall; near a stove on the other side of a wall.
3
Y2
Y1
RC
C
Second stage cool
4
First stage cool
5
Cooling power source (transformer +)
Common, system power -
Heating power source (transformer +)
First stage heat
●
Do not locate in unusual cooling conditions, such as:
6
on a wall separating an unheated room; or in a draft from
a stairwell, door, or window.
7
RH
W1
W2
E
8
●
Do not install the unit until all construction work and
9
Second stage heat
Emergency heat/Freeze protection
Heating Mode
Future Indoor temperature input -
Future Indoor temperature input +
Future Outdoor temperature sensor
input (a)
painting has been completed.
10
11
12
13
14
3.3. REMOVAL OF OLD UNIT
B
CAUTION: Read instructions carefully before removing any
wiring from existing thermostat. Wires must be labeled
before they are removed. When removing wires from their
terminals, ignore the color of the wires since they may not
comply with any standard.
TC
T
OT
15
OT
Future Outdoor temperature sensor
input (b)
●
Switch electricity to the furnace and air conditioner
OFF; then proceed with the following steps.
●
Remove cover from old thermostat. Most are snap-on
1.
G
The fan terminal is live at any time the
types and simply pull off. Some have locking screws on
the on the side. These must be loosened.
thermostat attempts to turn the system fan or
blower on.
●
Note the letters printed near the terminals. Attach
2.
O
This terminal is live at any time the unit is
labels (enclosed) to each wire for identification. Label and
remove wires one at a time. Make sure the wires do not
fall back inside the wall.
in Cool mode.
3. Y2 Activation of this terminal signifies that the
thermostat is calling for a second stage of cooling.
This terminal will remain inactive unless a second
stage compressor has been specified in the
installer setup menu.
●
Loosen all screws on the old thermostat and remove it
from the wall.
3.4. MOUNTING
CAUTION: Be careful not to drop the unit or disturb electronic
4. Y1 Activation of this terminal signifies that the
thermostat is calling for a first compressor stage.
This terminal will remain inactive unless at least
one compressor stage has been specified in the
installer setup menu.
parts.
●
Strip insulation 3/8 in. (9.5mm) from wire ends and
clean off any corrosion.
●
Fill wall opening with non-combustible insulation to
prevent drafts from affecting the thermostat.
5. RC This terminal provides power to the cooling
and fan terminals.
●
With each thumb on a release tab at the bottom of the
body, and fingers over the top of the unit. Release the
unit from its base plate by squeezing the tabs into the
body.
6.
C
Use of this terminal allows the unit to be
system powered rather than battery powered. Note
that the display backlight is battery powered only.
●
Separate the unit from its base plate by pulling the
7
RH This terminal provides power to the heating
body outward from the bottom.
terminals.
8. W1 This terminal is active when the thermostat
is calling for the first available stage of furnace or
electric heat. It will remain inactive unless at least
one stage of furnace type heat has been specified
in the installer setup menu.
NOTE: If you are mounting the base to a soft material like
plasterboard or if you are using the old mounting holes, the
screws may not hold. Drill a 3/16-in. (4.8mm) hole at each
screw location, and insert the plastic anchors provided. Then
mount the base as described below.
3
9. W2 This terminal is active when the thermostat
is calling for a second stage of furnace or electric
heat. It will remain inactive unless two stages of
heating have been specified in the installer setup
menu.
common to power the thermostat from the system in any
wiring configuration.
WARNINGS: 1. A B wire is sometimes used as a
common wire. Connecting a common B wire to the B termi-
nal in these systems will likely cause damage to the thermo-
stat and/or HVAC system. Do not connect a wire to the B ter-
minal if you are unsure whether it may be wired to a system
common.
10.
E
This terminal is active when the thermostat
is calling for Emergency heat in a heat pump sys-
tem. This terminal also powers freeze protection if
it is desired. It will be active below 40°F(5°C)
regardless of mode or battery condition or other
unforeseen condition.
2.If Both Y and C wire are present, then C is common. Tape it
off or connect it to the C terminal to allow the system to
power the thermostat.
11.
B
This terminal is live at any time the unit is
OPTIONAL C, X, B, TC
C
B
O
Transformer Common
in Heat mode.
B
O
Changeover Valve
12.TC Future indoor temperature sensor common.
May be wired to a maximum of three external
indoor sensor units.
Use O or B not both
3.5.5 SINGLE STAGE HEATING SYSTEM LABEL CROSS
REFERENCE
13.
T
Future indoor temperature sensor. May be
Previous Thermostat
Terminal Marking
RH, R, RC, V, 5
W, H, 4
New Thermostat
wired to a maximum of three external indoor sen-
sor units.
System
Terminals
RH
Wire To
All 2 Wire Heat
Transformer
Heating Valve
Transformer
Heat Control
*
14.OT Future first of two terminals dedicated to
the outdoor temperature sensor. Polarity of these
leads does not matter.
W1
3 Wire
RH, R, RC, V, 5
W, 4
RH
W1
15.OT Future second of two terminals dedicated to
the outdoor temperature sensor. Polarity of these
leads does not matter.
B, C
Tape Off *
3 Wire
(one wire is "F or G")
RH, R, 5, V
W, 4
RH
W1
G
Transformer
Heating Valve
Fan Relay
3.5.2 FREEZE PROTECTION
The PSP722E incorporates a mechanical thermal switch
which may be used to prevent a freeze-up by calling for
heat in the event the unit has accidentally been turned off
or its batteries have not been replaced as recommended.
G, F
3.5.6 SINGLE STAGE COOLING SYSTEM LABEL CROSS
REFERENCE
Previous Thermostat
Terminal Marking
RC, R, V
New Thermostat
●
This switch is available at the E terminal of the thermo-
System
2 Wire
Terminals
Wire To
stat. In most systems using this feature will require
wiring a jumper between the W1 and E terminals. The
thermostat will call then for the first stage of heat, in fur-
nace mode, or Aux heat in heat pump mode. See EMER-
GENCY HEAT.
RC
Y1
RC
Y1
G
Transformer
Cooling Relay
Transformer
Cooling Relay
Fan Relay
Y, Y1, C
3 Wire
RC, R, V
Y, Y1, C
G, F
●
The nominal temperature set point of this switch is
3.5.7 SINGLE STAGE FURNACE HEATING AND SINGLE
STAGE COOLING SYSTEM LABEL CROSS REFERENCE
40°F(5°C).
3.5.3 SPECIAL WIRING NOTES
Previous Thermostat
Terminal Marking
New Thermostat
Terminals
●
In heat pump mode, AUX heat is available at W1.
System
Wire To
●
In heat pump mode, Emergency Heat is activated from
4 Wire
the E terminal. This terminal also provides freeze protec-
tion and it will be active below a nominal temperature of
40°F(5°C).
(heat & cool with
single transformer)
RH, RC, R, V
W, W1
RH & RC, w jumper
Transformer
Heating Relay
Cooling Relay
Fan Relay
W1
Y1
G
3.5.4 COMMON WIRING OPTIONS
Y, Y1, C
G,F
Though not shown here additional second stages may be
used where applicable. Be sure to enable them properly
in the Installer Setup menu.
5 Wire
(heat & cool with
two transformers)
W2 is second stage heat
RH
RH
RC
W1
Y1
G
Heating Transformer
Cooling Transformer
Heating Relay
E
is emergency heat and freeze protection
RC
Y2 is second stage cool or second stage heat pump
W, W1
Y, Y1, C
G,F
Cooling Relay
OPTIONAL O or B terminals may be used to power heat-
ing dampers or changeover valves in any system config-
uration.
Fan Relay
3.5.8 TWO STAGE HEAT, SINGLE STAGE COOL, HEAT
OPTIONAL C terminal may be connected to a system
4
PUMP SYSTEM LABEL CROSS REFERENCE
Previous Thermostat
Terminal Marking
New Thermostat
Terminals
System
Wire To
Heat Pump
2 Heat, 1 Cool
RH, RC, R, V
RH & RC, w jumper
Transformer
Y, Y1, C
Y1
W1
E
Compressor Relay
Aux Heat Relay
Em Heat/Freeze Prot
*Changeover Valves
Use O or B not both
Fan Relay
W, W2
E
B
B*
O*
G
O
G,F
3.5.9 WIRING DIAGRAMS
TYPICAL INSTALLER SETUP:
TYPICAL 2 WIRE HEAT HOOKUP
24 VAC AND MILLIVOLT SYSTEMS
[0
]
1
SYSTEM TYPE = FURNACE
HEAT STAGES =1
COMPRESSOR STAGES = 0
MODES = Heat-Off
[0
]
2
[0
]
3
[04]
G
O
Y2 Y1 RC
C
RH W1 W2
E
B
[
]
09 HEAT FAN CONTROL
= GAS
NOTES:
JUMPER
PROVIDED
[
]
1
OPTIONAL COMMON
ALLOWS USE OF
SYSTEM POWER
SYSTEM
COMMON
GAS
VALVE
XFMR
AC LINE
TYPICAL INSTALLER SETUP:
TYPICAL 24VAC 3 WIRE HEAT HOOKUP
WHERE 3RD WIRE IS FAN WIRE
[0
]
1
SYSTEM TYPE = FURNACE
HEAT STAGES =1
COMPRESSOR STAGES = 0
MODES = Heat-Off
[0
]
2
[0
]
3
[04]
G
O
Y2 Y1 RC
C
RH W1 W2
E
B
[
]
09 HEAT FAN CONTROL
= GAS
NOTES:
JUMPER
PROVIDED
[
]
1
OPTIONAL COMMON
ALLOWS USE OF
SYSTEM POWER
SYSTEM
COMMON
GAS
VALVE
XFMR
FAN
AC LINE
5
TYPICAL INSTALLER SETUP:
TYPICAL 24VAC 4 WIRE HOOKUP
[0
]
1
SYSTEM TYPE = FURNACE
HEAT STAGES =1
COMPRESSOR STAGES = 1
MODES = Ht-Off-Cl-Auto
SINGLE STAGE HEATING AND COOLING
[0
]
2
[0
]
3
[04]
G
O
Y2 Y1 RC
C
RH W1 W2
E
B
[
]
09 HEAT FAN CONTROL
= GAS
NOTES:
JUMPER
PROVIDED
[
]
1
OPTIONAL COMMON
ALLOWS USE OF
SYSTEM POWER
SYSTEM COMMON
GAS
VALVE
COMPRESSOR
XFMR
FAN
AC LINE
TYPICAL INSTALLER SETUP:
TYPICAL 5 WIRE HOOKUP
SINGLE STAGE HEATING AND COOLING
[0
]
1
SYSTEM TYPE = FURNACE
HEAT STAGES =1
COMPRESSOR STAGES = 1
MODES = Ht-Off-Cl-Auto
[0
]
2
[0
]
3
[04]
G
O Y2 Y1 RC
C
RH W1 W2
E
B
[
]
09 HEAT FAN CONTROL
= GAS
NOTES:
[
]
1
OPTIONAL COMMON
ALLOWS USE OF
SYSTEM POWER
COOL
COMMON
COOLING
HEATING
GAS
VALVE
FAN
COMPRESSOR
XFMR 1
XFMR 2
AC LINE
AC LINE
6
TYPICAL INSTALLER SETUP:
TYPICAL SINGLE-STAGE HEAT PUMP WITH
(2 STAGES HEAT AND 1 STAGE COOL)
OPTIONAL AUX AND EMERGENCY HEAT
[0
]
1
SYSTEM TYPE = HEAT PUMP
HEAT STAGES =1
COMPRESSOR STAGES = 1
MODES = Ht-Off-Cl-
EmHt-Auto
[0
]
2
[0
]
3
[04]
G
O
Y2 Y1 RC
C
RH W1 W2
E
B
[
]
09 HEAT FAN CONTROL
= ELECTRIC
JUMPER
PROVIDED
NOTES:
[
]
1
OPTIONAL COMMON
ALLOWS USE OF
SYSTEM POWER
SYSTEM COMMON
[
]
2
USE "B" OR "O" BUT
SYSTEM AUX/EM REVERSING
COMPRESSOR
FAN
NOT BOTH
XFMR
HEAT
VALVE
[
3
]
AUX HEAT AND
EMERGENCY HEAT
ARE OPTIONAL
AC LINE
TYPICAL INSTALLER SETUP:
USE 2 SEPARATE SINGLE STAGE HEATERS
AS A 2 STAGE HEAT SYSTEM
[0
]
1
SYSTEM TYPE = HEAT PUMP
HEAT STAGES =1
COMPRESSOR STAGES = 1
MODES = Heat-Off
[0
]
2
[0
]
3
[04]
G
O Y2 Y1 RC
C
RH W1 W2
E
B
[
]
09 HEAT FAN CONTROL
= ELECTRIC
NOTES:
[
]
1
OPTIONAL COMMON
ALLOWS USE OF
SYSTEM POWER
SYSTEM 1
COMMON
SYSTEM 2
COMMON
HEATER
1
SYSTEM
XFMR 1
SYSTEM
XFMR 2
HEATER
2
AC LINE
AC LINE
7
TYPICAL INSTALLER SETUP:
MULTI-STAGE FURNACE HEAT
AND COOLING HOOKUP
[0
2
]
1
SYSTEM TYPE = FURNACE
[0
]
HEAT STAGES
=(MATCH SYSTEM)
[0
3
]
COMPRESSOR STAGES
G
O Y2 Y1 RC
C
RH W1 W2
E
B
= (MATCH SYSTEM)
[04]
MODES = Ht-Off-Cl-Auto
[
]
09 HEAT FAN CONTROL
= ELECTRIC
HEAT
COMMON
NOTES:
1
COOL
[
]
OPTIONAL COMMON
ALLOWS USE OF
SYSTEM POWER
EITHER SECOND
STAGE MAY BE
OMITTED
COMMON
HEATER
AIR CONDITIONER
COOLING HEATING
[
]
2
FAN
STAGE 2
STAGE 1
STAGE STAGE
XFMR
XFMR
COMPRESSOR COMPRESSOR
1
2
AC LINE AC LINE
TYPICAL INSTALLER SETUP:
TYPICAL MULTI-STAGE STAGE HEAT PUMP WITH
OPTIONAL AUX AND EMERGENCY HEAT
(2 OR 3 STAGES HEAT, 2 STAGES COOL)
[0
2
]
1
SYSTEM TYPE = HEAT PUMP
[0
]
HEAT STAGES
= MATCH SYSTEM
COMPRESSOR
[0
3
]
G
O
Y2 Y1 RC
C
RH W1 W2
E
B
STAGES = MATCH SYSTEM
MODES = Ht-Off-Cl-
EmHt-Auto
[04]
JUMPER
[
]
09 HEAT FAN CONTROL
PROVIDED
= ELECTRIC
NOTES:
SYSTEM COMMON
[
]
1
OPTIONAL COMMON
ALLOWS USE OF
SYSTEM POWER
HEAT PUMP
STAGE 2 STAGE 1
COMPRESSOR COMPRESSOR
SYSTEM AUX/EM REVERSING
FAN
[
]
2
USE "B" OR "O" BUT
XFMR
HEAT
VALVE
NOT BOTH
[
3
]
AUX HEAT AND
EMERGENCY HEAT
ARE OPTIONAL
AC LINE
8
3.6. INSTALL BATTERIES
3.7.1.2 HEAT STAGES
Install batteries at this time. For instructions, see BAT-
Set this to the number of non-compressor driven heat
TERY INSTALLATION.
stages to use for temperature control by this system.
3.7. INSTALLER SETUP
3.7.1.3 COMPRESSOR STAGES (COOL/HEAT PUMP
STAGES)
Configuration items are selected from the Installer Set up
Menu. They are stored in non-volatile RAM, and will be
preserved even in the event that the unit’s batteries are
run down, or removed, or the hardware reset on the rear
of the unit’s circuit board of the thermostat is pressed.
Set the number of compressor driven system stages to
use for temperature control. These stages include all
cooling or heat pump stages to be used for temperature
control by this system.
3.7.1.4 MODES
NOTE: Pressing the S/W RESET button on the rear of the
unit’s circuit board will write default values of all temperature
programs and setup menus into the unit nonvolatile memory.
Take care not to inadvertently press this button when the ther-
mostat has been removed from the wall plate!
The modes setting selects what system modes will be
available to the user. The selections available are system
mode dependant:
●
Heat-Off
●
Cool-Off
3.7.1 ACCESS AND NAVIGATE INSTALLER SETUP
MENU
Note: Insure that all relays are off before making changes in
the installer menu. There are two methods, which may be
used to do this. Place the unit in the OFF mode and wait for 5
minutes or Press the H/W RESET button on the rear of the
unit’s circuit board. Take care not to inadvertently press the
S/W RESET button.
●
Heat-Off-Cool
●
Heat-Off-Cool-Auto (Furnace Mode) or
●
Heat-Off-Cool-Em Heat-Auto (Heat Pump Mode)
3.7.1.5 MINIMUM RUN TIME
Minimum Run Time provides compressor protection and
prevents short cycling. Compressor stages are held off
for a minimum of this time. During program run this is
also the minimum on time.
●
To enter the Installer Setup Menu press and hold the
3.7.1.6 HEAT PUMP LOCKOUT
Setup Button for 10 seconds.
This menu item is available only in Heat Pump Mode with
an operational outdoor temperature sensor. Enabling this
option allows the thermostat to disable a heat pump and
request AUX Heat below the Heat Pump Lockout
Temperature.
●
Use the NEXT button to scroll through its options. As
you proceed the menu item number will be displayed in
the left portion of the screen.
●
Selections can be changed by pressing the UP/DOWN
button.
3.7.1.7 HEAT PUMP LOCKOUT TEMPERATURE
This menu item is available only in Heat Pump Mode with
an operational outdoor temperature sensor. With it you
may set the outdoor temperature at which the thermostat
will cease to call for heat pump sourced heat, and use the
alternate AUX Heat source.
●
Moving from one menu item to the next and accept-
ance of changes is done by pressing the NEXT button.
●
All changes become effective when the unit exits the
Installer Setup mode.
●
The Installer Setup mode will be exited when the Setup
button is pressed again, or, if no other keys are pressed
for 20 seconds.
3.7.1.8 DEADBAND
When using auto-changeover, deadband provides a disal-
lowed temperature range between the maximum heat
temperature set point and minimum cool temperature set
point. Deadband may be set from 3 to 5 degrees. With
auto-changeover active and the Deadband set to 3°F and
heat set to 70°F the minimum allowed cool temperature
set point will be 73°F. If the cool temperature set point is
lowered, then the heat temperature set point will be low-
ered by the same amount maintaining the 3°F Deadband.
All settings, their choices and default values are given in
INSTALLER SETUP MENU WITH FURNACE SYSTEM
TYPE SELECTED: and INSTALLER SETUP MENU WITH
HEAT PUMP SYSTEM TYPE SELECTED AND FUTURE
OUTDOOR SENSOR ENABLED.
3.7.1.1 SYSTEM TYPE
This option determines whether the thermostat is to con-
trol a furnace and air conditioning system or heat pump
system.
3.7.1.9 SWING 1
●
In furnace mode the unit will make the proper W ter-
Swing 1 sets the temperature variation the system allows
above the temperature set point before switching the first
stage heat source off, or below the temperature set point
before switching the first stage heat source on. In Cool,
Swing 1 sets the temperature variation the system allows
above the temperature set point before switching first
stage of cooling on, or below the temperature set point
before switching the first stage of cooling off.
minals live for Heating, and the proper Y terminals live
for cooling.
●
In Heat Pump mode the unit makes the proper Y ter-
minals live for the first and second stages of a heat pump
unit during heating or cooling. In this mode an additional
stage of Aux Heat may also be activated through the W1
terminal.
9
3.7.1.10 SWING 2
3.7.2 INSTALLER SETUP MENU WITH FURNACE SYS-
This value is similar to the Swing 1, but it controls the
temperature variation the system allows above and below
Swing 1’s lower limit before calling for a second stage.
Once a second stage is activated, it will remain on until
the temperature set point has been reached. If a third
stage of heat is present in heat pump mode, Swing 2 is
used to control it from the stage 2 lower limit.
TEM TYPE SELECTED:
Menu
Item
01
Display
Selections
Default
Furnace
2
System Type
Heat Stages
Compressor Stages
Modes
Furnace / Heat Pump
0 – 2
02
03
0 – 2
2
04
Heat-Off
*
Cool-Off
*
3.7.1.11 HEAT FAN CONTROL
Heat-Off-Cool
Heat-Off-Cool-Auto
*
Fossil fuel furnaces normally control the system fan while
the furnace is operating. Electric systems normally
require the thermostat to activate the fan. This setting
instructs the thermostat how to handle fan control during
heating. Electric heat and heat pumps generally require
the thermostat to activate the fan and therefore use the
electric setting.
*Heat-Off-
Cool-Auto
4 min
3°F(1°C)
0.25°F(0.15°C)
0.5°F(0.3°C)
Gas
05
06
07
08
09
10
11
12
13
14
15
Minimum Run Time
Deadband
1 to 5 min
3°F(1°C) to 5°F(3°C)
0.25°F(0.15°C) to 2.25°F(1.25°C)
0.25°F(0.15°C) to 2.25°F(1.25°C)
Gas / Electric
Swing 1
Swing 2
Heat Fan Control
Heat Fan On Delay
Heat Fan Off Delay
Cool Fan On Delay
Cool Fan Off Delay
Outdoor Sensor (future)
Internal Temp Sensor
(future)
3.7.1.12 HEAT FAN ON DELAY
0, 15, 30…180 sec
0, 15, 30…180 sec
0, 15, 30…180 sec
0, 15, 30…180 sec
NA/ON/OFF
0 sec
This setting allows the installer to program the length of
time between heating activation and fan activation (delay
on make).
0 sec
0 sec
0 sec
3.7.1.13 HEAT FAN OFF DELAY
NA/OFF
This setting allows the installer to program the length of
time between heating deactivation and fan deactivation
(delay on break).
ON/OFF
ON
16
17
18
Remote Sensor 1
(future)
3.7.1.14 COOL FAN ON DELAY
NA/ON/OFF
NA/ON/OFF
NA/ON/OFF
NA/OFF
NA/OFF
NA/OFF
This setting allows the installer to program the length of
time between cooling activation and fan activation (delay
on make).
Remote Sensor 2
(future)
Remote Sensor 3
(future)
3.7.1.15 COOL FAN OFF DELAY
This setting allows the installer to program the length of
time between cooling deactivation and fan deactivation
(delay on break).
3.7.3 INSTALLER SETUP MENU WITH HEAT PUMP
SYSTEM TYPE SELECTED AND OUTDOOR FUTURE
SENSOR ENABLED:
3.7.1.16 FUTURE OUTDOOR SENSOR
Menu
This setting enables and disables an outdoor sensor if it
is present. The setting will be held NA if a sensor is not
present, and will be reset to NA If the sensor is discon-
nected for any reason, including removal of the thermo-
stat from its base-plate, the thermostat will automatically
disable the sensor changing the setting in this menu
from ON to NA. With an outdoor sensor present and
enabled, the outdoor temperature will be displayed alter-
nately with time. The word OUT will be visible to the right
of the temperature while the outside temperature is dis-
played.
Item
01
Display
Selections
Furnace / Heat Pump
0 – 1
Default
System Type
Heat Stages
Compressor Stages
Modes
Furnace
02
1
03
0 – 2
1
04
Heat-Off
*
Cool-Off
*
Heat-Off-Cool
Heat-Off-Cool-
Em Heat-Auto
1 to 5 min
ON, OFF
*
*Heat-Off-Cool-
Em Heat-Auto
4 min
05
Minimum Run Time
Heat Pump Lockout
Heat Pump
06*
07*
Off
3.7.1.17 INTERNAL TEMPERATURE SENSOR
This setting enables and disables the thermostats internal
temperature sensor. It may only be disabled if there are
indoor remote sensors present and enabled.
3.7.1.18 FUTURE INDOOR REMOTE SENSOR 1, 2, 3
Used to enable and disable the respective remote sensors
in a system. When more than one indoor sensor is used,
the values of their measurements are averaged for use in
temperature control.
Lockout Temperature
Deadband
0°F- 50°F(-17°C-10°C)
3°F(1°C) to 5°F(3°C)
0.25°F(0.15°C) to 2.25°F(1.25°C)
0.25°F(0.15°C) to 2.25°F(1.25°C)
Electric
0°F(-17°C)
3°F(1°C)
0.25°F(0.15°C)
0.5°F(0.3°C)
Electric
08
09
10
11
12
13
14
15
Swing 1
Swing 2
Heat Fan Control
Heat Fan On Delay
Heat Fan Off Delay
Cool Fan On Delay
Cool Fan Off Delay
0, 15, 30…180 sec
0 sec
0, 15, 30…180 sec
0 sec
0, 15, 30…180 sec
0 sec
0, 15, 30…180 sec
0 sec
10
16
Outdoor Sensor
(future)
4.1.3 DEFAULT PROGRAM
●
NA/ON/OFF
ON / OFF
NA/OFF
ON
As supplied from the factory, the following ENERGY
17
18
Internal Temp Sensor
Remote Sensor 1
(future)
STAR approved program will be used for temperature
control. This program and all other settings maybe
restored to their default values via a SOFTWARE RESET.
NA/ON/OFF
NA/ON/OFF
NA/ON/OFF
NA/OFF
NA/OFF
NA/OFF
●
19
20
Remote Sensor 2
(future)
Default Daily Temperature Program
Period
Morning
Day
Heat Mode
Cool Mode
Remote Sensor 3
(future)
6:00 AM 70°F
8:00 AM 62°F
6:00 PM 70°F
10:00 PM 62°F
6:00 AM 78°F
8:00 AM 85°F
6:00 PM 78°F
10:00 PM 82°F
*Available only with an outdoor sensor present and
enabled
Evening
Night
3.7.4 COMPLETING YOUR INSTALLATION
4.1.4 MODES
●
Turn the power back on to your heating and/or air con-
Because of your thermostats great versatility not all
modes will be applicable to your application. The mode
selections available to you are determined by settings in
the Installer Setup Menu. Often the unit’s mode is dis-
played during program run. When a unit has first been
powered up with the dial in the Run position, your ther-
mostat will begin to control your heating and/or air con-
ditioning system according to it’s default ENERGY STAR
approved program in AUTOCHANGE mode.
ditioning system.
●
Verify that the system and its fan are operating proper-
ly. When set to a high temperature, the heating system
should provide warm air after a short time. Likewise a
cooling system should provide cool air after a short time.
Usually sound from the furnace and air conditioning units
can be heard while they are running. The rush of moving
air should be heard within a short time after either has
been started.
4.1.4.1 OVERRIDE
NOTE: If you have an electric system and the blower does not
operate after installation, verify that the electric/gas option in
installer set up is set to Electric.
During run, either the Heat or Cool set point temperature
may be altered with the temperature UP/DOWN arrow
button. T Override will be displayed in line two of the dis-
play. The adjusted temperature will remain the set tem-
perature until the next program period begins. Then, tem-
perature settings will return to program control.
●
Installation is now complete.
4. OPERATION
4.1. OPERATING BASICS
4.1.1 UP/DOWN ARROW CHANGE KEYS
There are two arrow keys just the right of the units dis-
play. They are used to adjust set temperatures, and
change other settings.
4.1.4.2 HOLD
Press this button to indefinitely maintain a fixed tempera-
ture. HOLD will be displayed in line two of the display.
●
Press this button once to enter permanent temperature
HOLD from program run or temperature OVERRIDE.
4.1.1.1 TEMPERATURE ADJUSTMENT
●
●
Pressing this button again will toggle HOLD off return-
Pressing an arrow key once adjusts a set temperature
ing to program RUN.
by one degree in the associated direction.
❷
Holding the key will automatically advance the setting
4.1.4.3 AUTOCHANGE
in the associated direction.
4.1.1.2 CHANGING OTHER SETTINGS
The AUTOCHANGE mode allows your thermostat to
switch between Heat and Cool modes of temperature
control automatically.
If there are many choices for a value, usually that setting
will automatically advance by holding one of the arrow
keys. Some settings though, must be changed one press
at a time.
●
AUTOCHANGE may not be available or applicable in
your installation.
●
To enter AUTOCHANGE mode if it is available, press
the MODE button repeatedly until the display indicates
that the unit is in AUTOCHANGE mode.
4.1.2 SET DAY AND TIME
The time used by your thermostat for temperature con-
trol is that displayed by the unit. To set the correct time
after the unit has been unpowered or after software reset:
●
In AUTOCHANGE mode, you can determine whether
your thermostat will call for heating or cooling (at that
time) by whether HEAT SET or COOL SET is visible on
the units display.
●
Open the drop down door on the front of the thermo-
stat. Rotate the dial to the SET DAY/TIME position. Use
the UP key to advance the day to the current day of the
week.
●
To switch from heating to cooling or vise versa, press
both arrow keys at the same time.
●
Pressing the UP/DOWN temperature arrow keys will
●
Press NEXT to adjust the time. Pressing NEXT again
adjust the active, visible set temperature.
will toggle from Set Day to Set Time.
●
When AUTOCHANGE is first entered, the unit may
●
Use the UP or DOWN key to set the thermostats clock.
need to determine which if either heating or cooling is
●
Return the dial to its RUN position.
11
required. Heating and cooling set temperatures may not
be adjusted until heating or cooling is necessary, or one
of these modes is manually selected by pressing and
releasing both arrow keys at the same time.
button is pressed again, or if no other keys are pressed
for 20 seconds.
4.2.2 KEYBOARD LOCK
Two types of Keyboard locks allow owners/operators to
prevent unauthorized changes to the thermostats set-
tings. The two types of locks are full and partial. When
the thermostat is locked, a three digit code is set. That
code must be reentered before locked settings can be
changed without performing a software reset off the unit.
●
You can force heating or cooling to be the active mode
by pressing and releasing both arrow keys at the same
time until the desired mode is indicated. After, the unit
will then switch modes as necessary to control tempera-
ture.
4.1.4.4 HEATING
Entering a code toggles the selected lock on or off. While
a lock is effective, a padlock is shown near the lower
right corner of the screen.
●
Press the MODE button repeatedly until the word HEAT
is shown along the top of the display. The unit is in HEAT
mode ready to control your heating system.
4.2.2.1 PARTIAL KEYBOARD LOCK
●
Press temperature UP or DOWN keys until your
A partial lock allows other users to adjust only the tem-
perature set point to values at or between the Maximum
Heat Setting and Minimum Cool Settings.
desired temperature is displayed in the HEAT SET area of
the display.
●
While heating is active, a flame icon will flash above
4.2.2.2 FULL KEYBOARD LOCK
the HEAT SET temperature. If a second stage of heat is
A full lock disables all the keys except the Setup button
on the front, and the S/W Reset button on the rear.
Pressing the S/W Reset button will rewrite all settings
and programs to their default values.
called for the flashing rate increases.
4.1.4.5 COOLING
●
Press the MODE button repeatedly until the word
COOL is shown along the top of the display. The unit is in
Cool mode ready to control your air conditioner.
4.2.2.3 SETTING THE LOCK
1. Press SETUP.
●
Press temperature UP or DOWN keys until your
2. Select Full or Partial.
desired temperature is displayed in the COOL SET area of
the display.
3. Press NEXT.
4. Set code one digit at a time. Press NEXT after each
digit.
●
While cooling is active, a snowflake icon will flash
above the COOL SET temperature. If a second stage of
5. When NEXT is pressed after the third digit has been
entered, the unit will be appropriately locked.
4.2.2.4 CLEARING A LOCK
heat is called for the flashing rate increases.
4.1.4.6 OFF
●
Press the MODE button repeatedly until the display
1. Press SETUP.
indicates that the unit is in OFF.
2. Enter code one digit at a time. Press NEXT after each
digit.
●
Heating and cooling will be disabled.
●
Periods programmed to maintain a minimum fan run
3. When NEXT is pressed after the third digit has been
entered, the unit will be unlocked if the correct code was
entered.
time will continue do so.
4.1.5 DISPLAY ILLUMINATION
●
Press the light bulb button to illuminate the display.
Pressing other buttons will keep the display illuminated
until no button has been pressed for approximately 20
seconds.
4.2. USER SETUP MENU
User selectable options are available from the User Setup
Menu. To access the User Setup Menu press the Setup
button. All settings, their choices and default values are
given in the USER SETUP MENU:.
4.2.2.5 CHANGING THE LOCK CODE
1. Press SETUP.
2. Select NEW CODE.
3. Press NEXT.
4.2.1 ACCESS AND NAVIGATE USER SETUP MENU
4. Enter old code one digit at a time. Press NEXT after
each digit.
●
To scroll through the User Setup Menu one item at a
time, momentarily press Setup Button.
5. Enter new code one digit at a time. Press NEXT after
each digit.
●
Selections can be changed by pressing the UP/DOWN
button.
6. When NEXT is pressed after the new third digit has
●
Moving from one menu item to the next and accept-
been entered, the new code will be effective.
ance of changes is done by pressing the NEXT button.
4.2.3 BEEP
●
All changes become effective when the unit exits the
This option allows the audible feedback tone (Beep) to be
enabled or disabled.
User Setup mode.
●
The User Setup mode will be exited when the Setup
12
4.2.4 TEMPERATURE DISPLAY FORMAT (F/C DISPLAY) grammed for. A general rule of thumb is to assume that
Temperature may be displayed in Fahrenheit or Celsius
with this option.
the fan will run at 1/3 duty cycle. A 90 day filter will then
be good for 90*24/3=720 hours. This is the default value.
Setting the filter counter limit to 0000 will disable the
change filter indicator. Valid entries are from 0 to
2000hrs.
4.2.5 CLOCK FORMAT
The time shown on the thermostats clock may be dis-
played in 12 or 24 hour format. Set this option to your
preference.
4.2.11 USER SETUP MENU:
Menu
4.2.6 CALIBRATION OFFSET
Item
01
02
03
04
05
06
07
08
09
Display
Selections
Default
NO
Your thermostat is accurately calibrated at the factory to
within 1°F An offset value up to 5°F may be added to
the temperature value that the thermostat measures. This
may allow you to match this thermostat to another.
LOCK KEYPAD
BEEP
NO, PARTIAL, FULL, NEW CODE
ON, OFF
ON
°F/°C DISPLAY
CLOCK FORMAT
CALIBRATION OFFSET
MAX HEAT TEMP
MIN HEAT TEMP
EARLY RECOVERY
FILTER LIMIT
°F, °C
°F
12HR / 24HR
5°F ( 3°C)
12HR
0°F
4.2.7 MAXIMUM HEAT SETTING
The temperature that this option is set to will be the high-
est HEAT SET temperature available in run mode or while
programming the thermostat.
45°F-90°F (7°C-32°C)
45°F-90°F (7°C-32°C)
ON, OFF
90°F (32°C)
45°F (7°C)
OFF
4.2.8 MINIMUM COOL SETTING
0-2000HRS
720HRS
The temperature that this option is set to will be the low-
est COOL SET temperature available in run mode or while 4.3. ADVANCED FEATURES AND OPERATION
programming the thermostat.
4.3.1 EMERGENCY HEAT
●
To use an emergency heat system, press the MODE
4.2.9 SMART RECOVERY
button repeatedly until the EMER HT is shown along the
top of the display. The unit is in emergency heat mode
ready to control your emergency heating system. In heat
pump systems, the emergency heat terminal is often
wired to W1 the AUX heat terminal.
Your thermostats Smart Recovery allows your HVAC sys-
tem to attempt to recover from a setback period and
reach your desired comfort temperature set point by the
beginning of your programmed comfort period. This
option allows you to choose whether to use Smart
Recovery.
●
Press temperature UP or DOWN keys until your
desired temperature is displayed in the HEAT SET area of
the display.
If enabled, Smart Recovery will initiate if:
●
Recovery is valid only from a night setback to morning
●
Freeze protection is also provided at this terminal. See
comfort or day setback to evening comfort period.
FREEZE PROTECTION.
●
In Heat mode the temperature set point of the comfort
4.3.2 FAN MODES
period must be higher than the setback period.
Your thermostat provides three fan modes. They are
AUTO, CLEAN, and ON. The fan may be controlled by
your units program, or the program may be overridden
by pressing the FAN button and selecting another mode.
Appropriate indicators are visible along the top of the
units display when active.
●
In Cool mode the temperature set point of the comfort
period must be lower than the setback period.
●
The estimated Smart recovery time must be longer
than 15 minutes for an Smart recovery to be initiated.
●
Maximum Smart recovery time is one hour.
●
AUX heat will not be activated during the first half hour
of a Smart recovery. Then it will only be activated if nec-
essary to achieve the programmed temperature by the
beginning of the next period.
4.3.2.1 FAN AUTO
FAN AUTO denotes that the fan will run only to fulfill your
heating and cooling requirements.
●
The Smart recovery temperature set point must be
4.3.2.2 CLEAN
This enables the CLEAN CYCLE® feature. The FAN icon
alone in the display denotes that the fan is maintaining
the programmed minimum run time; it will also run addi-
tional time as required to maintain temperature control.
The algorithm used avoids additional fan time when the
minimum run time has been met over the last hour
through temperature control. Minimum fan run times are
met by running one third the hourly requirement at twen-
ty minute intervals.
achievable. If a desired smart recovery is repeatedly
ignored by your thermostat that is an indicator that you
should modify your program so that the recovery can be
achieved within the 1 hour limit.
●
A Smart recovery may not be initiated for 48 hours
after the units programs have been changed. This allows
the unit to gather the data necessary to predict a Smart
recovery time.
4.2.10 FILTER LIMIT
Your thermostat will warn you that your HVAC systems
air filter should be changed after the systems fan has run
the number of hours that this setting has been pro-
4.3.2.3 FAN ON
FAN ON denotes that your system fan will run continu-
ously.
13
●
●
●
●
●
●
Today’s cumulative heating time
Today’s cumulative cooling time
Yesterdays cumulative heating time
Yesterdays cumulative cooling time
Total cumulative heating time
4.3.3 VACATION HOLD
Use this feature to instruct the thermostat to hold a fixed
temperature for a period of from 1 to 30 days.
●
Verify that the unit is in Heat, Cool or AUTOCHANGE
Total cumulative cooling time
with a temperature set point visible. The unit must be
have a temperature set point visible to enter Vacation
Hold mode.
To view this set of timer values:
●
Rotate the dial to the ENERGY USAGE position. Timer
values will repeatedly display the above sequence.
●
Press and hold the HOLD button for approximately
●
The cumulative timers may be reset by pressing the
three seconds.
UP or Down arrow key once. Pressing an arrow key
again will toggle between 00:00 and the current value.
Pressing the UP or Down arrow key also stops the scroll-
ing.
●
Use the UP/DOWN arrow keys to adjust the number of
days to your preference. The maximum number of
allowed days is 30.
●
Press NEXT. The thermostat will display the number of
●
Press NEXT to resume scrolling.
days remaining in this Vacation Hold.
●
When you rotate the dial to another mode, the current
●
If the unit is in Heat mode, it will now maintain a mini-
values will be the values retained in memory. Leave the
mum temperature by controlling your heating system. If
the unit is in Cool mode, it will now maintain a maximum
temperature by controlling your cooling system.
value at 00:00 to reset the cumulative timers.
4.3.7 FUTURE OUTDOOR SENSOR
An optional outdoor sensor may be installed to enable
the thermostat to display the temperature outside your
home. This sensor may also be used to instruct the unit
to switch from a heat pump to another source of heat.
Once installed the outdoor temperature will alternate with
the time in the display. To install an outdoor sensor refer
to the Installation Section of this manual. To enable an
outdoor sensor or change heat pump settings refer to the
Installers Setup Section of this manual.
●
The Vacation Hold will be complete when there are no
remaining days left and the unit will resume using the
temperature programs stored in its memory.
●
A Vacation Hold may also be terminated prematurely
by Pressing the HOLD button again, changing the mode
of the system, or rotating the dial.
4.3.4 DAYLIGHT SAVINGS TIME ADJUSTMENT (DST)
This button is labeled DST. When pressed it shifts the
units clock time in a three press sequence. A first press
will add 1 hour to the displayed time. A second press
subtracts one hour from the original time, and a third
press returns the unit to the original time. After one
minute with no new DST button presses, the sequence is
reset staring with the current displayed time.
4.3.8 FUTURE REMOTE INDOOR SENSORS
Up to three optional indoor sensors may be installed. The
temperature measurements of all active indoor sensors
will be averaged and used in temperature control. With
remote indoor sensors functioning, the units’ internal
temperature sensor may be enabled or disabled to allow
the thermostat to be mounted in locations that would
otherwise be non-ideal.
4.3.5 AIR FILTER
This unit incorporates a timer, which records the number
of hours the thermostat has activated the fan. This timer
is intended to indicate when your HVAC systems filter
should be cleaned or replaced.
To install indoor temperature sensors refer to the
Installation Section of this manual. To enable or disable
the units internal sensor or other remote indoor tempera-
ture sensors refer to the Installers Setup Section of this
manual.
●
Refer to the User setup menu to set the number of
hours the timer will use to indicate that changing the filter
is recommended.
●
To view the number of hours the thermostat has acti-
4.3.9 RESET
vated the fan since the last timer reset, rotate the dial to
the AIR FILTER position.
There are two RESET buttons on the rear of the unit’s cir-
cuit board. They are the Hardware and Software RESET
buttons.
●
To reset the timer press the UP or Down arrow key
once. Pressing an arrow key again will toggle between
0000 and the current value. The value in display when
you exit this mode will be the value retained in memory.
Leave the value at 0000 to reset the timer.
4.3.9.1 HARDWARE RESET (H/W RESET)
The H/W RESET button restarts your thermostats pro-
gram at the beginning of normal operation. This button is
generally of little use to an owner.
●
To exit the AIR FILTER mode, rotate the dial to another
position.
4.3.9.2 SOFTWARE RESET (S/W RESET)
4.3.6 ENERGY USAGE
Your thermostat records the total number of hours the
thermostat has activated heating and cooling with six
separate timers. They measure:
The S/W RESET button restarts your thermostats pro-
gram at initialization. It may be used to reset every pro-
grammable value to it’s default setting.
14
ing the settings for that day.
●
Rotate the dial back to RUN to and accept all current
Pressing this button will write default values of all
temperature programs and setup menus into the unit’s
nonvolatile memory. Take care not to unintentionally
press this button when the thermostat has been
removed from the wall plate!
values and end the programming session.
4.4.2 WEEKDAY FAN PROGRAMMING
Programming fan operation is similar to programming
the temperature periods and set points. Fan periods are
independent of temperature periods and are designated
P1, P2, P3, P4.
4.4. PROGRAMMING
You can change the preset time/and temperatures to suit
your schedule for each day of the week. Each day has
four consecutive periods. They are Morning, Day,
Evening, and Night. Separate set points are provided for
Heat and Cool.
●
Rotate the dial to Set Weekday Programs, then press
and hold the FAN button for over 2 seconds.
●
The fan day and period will be displayed in the top
center and right portion of the screen. The bottom por-
tion will show the fan mode and start time for that period.
The fan mode for this period will be flashing to indicate
that it may be changed with the UP/DOWN arrow keys.
Choices are:
Fan programming is similar to temperature program-
ming. It has four consecutive periods, which are inde-
pendent of the four temperature periods. The default set-
ting for your systems fan requires it to run only as
required by your environmental system. It may be pro-
grammed to maintain a minimum run time on an hourly
basis, or run continuously.
■
Auto: default value; the fan will run only when neces-
sary for your HVAC system to maintain temperature con-
trol.
■
Program: This mode will insure that during every
4.4.1 WEEKDAY TEMPERATURE PROGRAMMING
hour, the fan will run for the for at least the number of
minutes shown at the top left of the display, beginning at
the displayed time for this period until the beginning of
the next period. If your heating or cooling requirement
fulfills the minimum fan run time, additional fan run time
will not be requested. Activation of the fan when neces-
sary is done at twenty minute intervals for one third the
hourly run time.
●
Rotate the dial to Set Weekday Programs. The heat
and cool set points will be displayed on the left side of
the display. The start time for the displayed day will flash
to show that this is the setting currently ready for edit.
●
Use the up or down arrow keys to change the start
time for this period. One period ends at the start time of
the next period. The beginning of that period may not be
any closer to the beginning of the next period than one
15 minute increment.
■
On: The On setting will run the fan continuously dur-
ing this period.
●
Press NEXT to accept the displayed start time and
●
Set the desired Fan mode for his period. Press NEXT
advance to edit the heat set point. It will be flashing.
to advance and edit this periods start time.
●
Use the up or down arrow keys to change Heat Set to
●
Use the UP or DOWN arrow keys to change the start
the temperature you desire.
time. A period ends at the start time of the next period.
The beginning of a period may not be any closer to the
beginning of the next period than one 15 minute incre-
ment.
●
Press NEXT to accept the displayed heat set point to
the temperature and advance to edit the cool set point. It
will be flashing.
●
There is a minimum value that must be maintained
●
Press NEXT to advance and set the minimum fan run
between the heat temperature set point and Cool temper-
ature set point. The value that must be maintained is
called the Deadband. It is programmable and may be
changed in the Installer Setup menu. If you move the
heat set point temperature to close to the cool set point
temperature the cool set point temperature will move
away from the heat set point temperature to maintain the
dead band. Conversely the heat set point temperature will
move if you adjust the cool set point temperature to
close. There are programmable limits for both heat and
cool, which you will not be able to exceed. These values
are accessible from the User Setup Menu.
time if this period is to use program mode.
●
Pressing NEXT again will bring you to the next period’s
mode.
●
When all the periods for a day have been set, the start
time for the next weekday will be displayed to begin edit-
ing the settings for that day.
●
The sequence of days that you may program pro-
gresses the weekdays MON - FRI, and repeats.
●
Then press and hold the FAN button for over 2 sec-
onds to return to Weekday temperature editing or rotate
the dial back to RUN to and accept all current values and
end the programming session.
●
When you have changed the Cool set point to your
desired temperature, press NEXT to advance to the next
period. Its start time will be flashing indicating that it is
under edit.
4.4.3 WEEKEND PROGRAMMING
Weekend programming is identical to weekday program-
ming except rotate the dial to set weekend programs, and
the sequence of days that you may program is SAT, SUN
and then repeating this two day sequence.
●
When all the periods for a day have been set, the start
time for the next weekday will be displayed to begin edit-
15
Stage one of a cooling system will be deactivated at the
value of swing 1 below the temperature set point.
4.4.4 COPY PROGRAMMING
●
The COPY button allows you to easily copy temperature
or fan programs from any day, to any other day, to all
weekdays, to both weekend days, or all days. The Copy
function copies only the temperature or fan program
from a day, not both at the same time. To copy a day’s
temperature or fan programs from one day to others:
Stage two of a heating system will be activated at the
value of (swing 1 + swing 2) below the temperature set
point. The auxiliary heat indicator AUX HT will be visible
when a second stage of heat is activated. Stage two of
cooling will be activated at the value of (swing 1 + swing
2) above the temperature set point.
●
●
In the appropriate programming mode press COPY.
Stage two of a heating or cooling system will be deac-
The display will show COPY FROM with current day
being programmed flashing below.
tivated at the temperature set point.
●
Stage three of a heating system will be activated at the
●
Use the UP or DOWN arrow buttons to select the day
value of (swing 1 + 2*swing 2) below the temperature
set point.
you want to copy from. Selections are:
Any single day, SUN - SAT
●
Stage three of a heating or cooling system will be
All weekdays MON to FRI
deactivated at the temperature set point.
Both weekend days SAT and SUN
All days at once SUN – SAT
7. TECHNICAL ASSISTANCE
If you have any problems installing or using this thermo-
stat, please carefully and thoroughly review the instruc-
tion manual. If you require assistance, please contact our
Technical Assistance Department at 856-234-8803 during
regular business hours between 8:00AM and 4:30PM
Eastern Standard Time, Monday through Friday. You can
also receive technical assistance online anytime day or
offers you answers to the most common technical ques-
tions, and also permits you to email your questions to
our technical support staff at your convenience.
●
Press NEXT.
●
Again use the UP or DOWN arrow buttons to select the
day or days you want to copy.
●
Press NEXT to accept the displayed copy to days, and
the copy will be complete.
5. BATTERIES/MAINTENANCE
Depending on your installation, your unit may require
batteries to control your HVAC system. If required,
replace your thermostat’s batteries at least once a year or
when the battery symbol appears in the display.
5.1. BATTERY INSTALLATION
8. WARRANTY
1. Remove fresh batteries from their carton.
2. Remove body of thermostat as described during
installation.
Limited Warranty: If this unit fails because of defects in
materials or workmanship within three years of date of
original purchase, LUX Products Corporation will, at its
option, repair or replace it. This warranty does not cover
damage by accident, misuse, or failure to follow installa-
tion instructions. Implied warranties are limited in dura-
tion to three years from date of original purchase. Some
states do not allow limitations on how long an implied
warranty lasts, so the above limitation may not apply to
you. Please return malfunctioning or defective units to
the participating retailer from which purchase was made,
along with proof of purchase. Please refer to "TECHNICAL
ASSISTANCE" before returning thermostat. Purchaser
assumes all risks and liability for incidental and conse-
quential damage resulting from installation and use of
this unit. Some states do not allow the exclusion of inci-
dental or consequential damages, so the above exclusion
may not apply to you. This warranty gives you specific
legal rights and you may also have other rights which
vary from state to state. Applicable in the U.S.A. only.
3. Remove the used batteries if present and replace them
within 90 seconds to avoid having to reset the day and
time.
4. Install two new “AA” size Energizer or Duracell alkaline
batteries in the battery compartment. Observe the polari-
ty marking shown in the compartment.
WARNING: Use Energizer® or DURACELL®
Alkaline Batteries Only.
5. Place the thermostat body back on the wall.
NOTE: Replace your thermostat’s batteries with new alkaline
batteries at least once a year or when the battery symbol
appears in the display.
The use of high quality alkaline batteries is absolutely
required for your thermostat to operate properly.
6. TECHNICAL DETAILS
6.1. STAGING
●
Stage one of a heating system will be activated at the
value of swing 1 below the temperature set point. Stage
one of a cooling system will be activated at the value of
swing 1 above the temperature set point.
●
Stage one of a heating system will be deactivated at
the value of swing 1 above the temperature set point.
16
|